Please send RFIs and RFQs to stan@securepower.io

Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
  • Load image into Gallery viewer, Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
  • Load image into Gallery viewer, Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
  • Load image into Gallery viewer, Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS
  • Load image into Gallery viewer, Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS

Schneider Electric Galaxy VX 750kVA UPS, 480V, Start up 5x8, GVX750K750NGS

Regular price
$154,599.92
Sale price
$154,599.92
Regular price
Sold out
Unit price
per 

GVX750K750NGS Features

Key Features

Output power capacity
750.0kWatts / 750.0kVA
Output Connections
(1) Hard wire 4-wire (3P + E) (Battery Backup)
Nominal Output Voltage
480V 3PH
Nominal Input Voltage
480V 3PH
Input Connections
Hard wire 4-wire (3P + E)
A highly efficient, modular, 750 kVA 3-phase UPS that provides the performance, flexibility, and maximized asset utilization today’s large data centers and mission critical applications require. This EcoStruxure Ready UPS features up to 99% efficiency with patented ECOnversion technology. Includes 5x8 start-up service.
Includes: Installation guide, Network management card, Seismic compliance, Start-up service, Top and bottom cable entry

  • Facility-friendly design
    Features a wide input voltage window and input power factor correction, limiting impact on batteries and facility infrastructure.
  • Flexible operating modes
    Offers three operating modes to meet your business requirements. With ECOnversion Mode, ECO Mode, and normal operation, you can choose one mode or a combination of all three to achieve the efficiency and performance ratings your site requires.
  • Integrated parallel up to 4+1
    Includes support for parallel configurations up to 4+1 (4 for capacity and 1 for redundancy), allowing easy expansion and additional redundancy.
  • Patented 4-level inverter
    Innovative inverter design delivers high efficiency and low operating costs, while increasing reliability by reducing stress on each IGBT.
  • Scalable for capacity or redundancy
    Provides N+1 redundancy without sacrificing load capacity; cabinets can be added after initial installation.
  • Smart Power Test (SPoT)
    Perform UPS test without a load bank and perform full charger testing with minimal battery use.

Galaxy VX Features & Benefits

Serviceability

5x8 Start-up service included
Required for full coverage of factory warranty
StruxureWare Data Center Expert compatible
Enables centralized management via StruxureWare Data Center Expert.
StruxureOn enabled
Simplify maintenance and operation of your equipment through the use of vendor-neutral, cloud-based software and services.
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
Multiple levels of service
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.

Availability

Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
Parallel-capacity capable
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
Internal backfeed protection
Increases system defense from power anomalies.
Energy storage flexibility
Conventional flooded and modular battery offer along with different charging modes allows tailoring to specific back-up requirements.
Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability. br /Click a href="http://www.schneider-electric.com/b2b/en/solutions/system/s4/data-center-and-network-systems-lithium-ion-battery/index.jsp"; target="_blank"here/a for more details.

Total cost of Ownership

ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Input Power Factor Correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
ECOnversion mode
Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.
Wide input voltage range
Designed for harsh electrical environments to save battery life.
Robust operation
No power derating in kW up to 40 degrees C or 104 degrees F.

Technical Specifications

Output

Max Configurable Power (Watts)
750.0kWatts / 750.0kVA
Output Frequency (sync to mains)
60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised, 60 Hz Sync to mains
Load Crest Factor
3 : 1
Topology
Double conversion online
Waveform type
Sine wave
Overload Operation
10 minutes at 125% and 60 seconds at 150%
Output Voltage THD
< 2% linear load and < 3% non-linear load
Output Voltage Tolerance
+/- 1% symmetrical load and +/- 3% asymmetrical lo
Bypass
Built-in static bypass, Optional external bypass

Input

Input frequency
40 - 70 Hz
Input voltage range for main operations
408 - 600V
Input Total Harmonic Distortion
Less than 3 % for full load
Maximum Short Circuit Withstand (Icw)
100.0kAmps
Input Power Factor at Full Load
0.99

Batteries & Runtime

Battery type
External battery system
End of Discharge Battery Voltage
384 V DC
Efficiency